Permit: T17CM07419

Parcel: 12213055E

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T17CM07419

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/27/2017 PLUMBING - FINAL Approved REVIEW OF WATER CHLORINATION COMPLETE
11/08/2017 PLUMBING - FINAL Denied 1- SHALL PROVIDE A VACUUM BREAKER FOR ALL SHAMPOO BOWLS. REFERENCE 608.1 IPC.
2- SHALL PROVIDE THE LISTING FOR THE SHAMPOO SINKS.
3- SHALL LABLE ALL CIRCUIT BREAKERS IN THE SERVICE PANEL.
4- SHALL PROVIDE A P-TRAP FOR SHAMPOO SINKS IF LISTING DOES NOT INCLUDE THEM IN INSTALLATION STANDARD.
11/08/2017 PLUMBING - FINAL Partial Approval
09/29/2017 PLUMBING - FINAL Prior to Final Inspectn PROVIDE WATER CHLORINATION REPORT