Permit: T17CM07401

Parcel: 13632003H

Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Date Description Inspector Results Comments
06/06/2018 STEM WALL/RETAINING WALL Approved
05/03/2018 STEM WALL/RETAINING WALL Not ready for Inspection STEM WALL RETAINING WALL HAS BEEN POURED. NEED PROOF THAT THE 2 LIFTS ON THE RETAINING WALL WERE INSPECTED BEFORE CAN GIVE APPROVAL. ACCORDING TO DRAWINGS RETAINING WALLS OVER 4' NEED COMPACTION TESTS AND SPECIAL INSPECTION CERT. THAT WAS NOT PROVIDED TO ME EITHER.
03/14/2018 STEM WALL/RETAINING WALL Denied UPON REVIEW WITH PRIOR INSPECTORS, RE BAR AND BONDBEAM, AND WIRE HAD NOT BEEN INSPECTED AT ALL, EVERY 4 LIFTS SHOULD HAVE BEEN INSPECTED BUT CLEARLY WAS NOT, OWNER/BUILDER DID BOT HAVE PRINTS OR PERMITS ON SITE, OWNER STARTED TO BUILD RETAINING WALL ON 01/18/18 WITHOUT REVISED PRINTS AND OR STAMP FROM CITY APPROVAL, BUILDER ALSO TRIES TO CONVEY THAT INSPECTORS GAVE HIM VISUAL APPROVAL, WHEN IT IS COMMON KNOWLEDGE, THAT IF AN ITEM WAS APPROVED IT SHALL BE WRITTEN DOWN.