Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
Permit Number - T17CM07142
Inspection Description - PLUMBING - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2017 | PLUMBING - FINAL | Denied | ALL WATER HEATER VENTING NEEDS TO BE CHECKED FOR PROPER VENT CONNECTORS. CAPS AT VENT TERMINATIONS ARE NOT APPROVED FOR GAS VENTING. UNIT 17 VENT IS NOT CONNECTED. PROVIDE T & P DRAINS AT WATER HEATERS. PROVIDE 3 SCRWES IN ALL VENT CONNECTOR JOINTS. | |
09/21/2017 | PLUMBING - FINAL | Approved | ||
09/20/2017 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 * |