Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
Permit Number - T17CM07023
Inspection Description - PLUMBING - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2018 | PLUMBING - FINAL | Partial Approval | MAN HOLE 1 .7 DROP 15 SECS MANDRELL TEST MANHOLES 3 TO 4, 2 TO 3, 2 TO 1 TO SEWER MAN HOLE 2 .8 DROP 15 SEC DI NOT WITNESS VACUMN TEST MAN HOLES 3 AND 4 PROBLEMS WITH LEAKS AT GASKET MAN HOLES 1 NAD 2 WITNESSED VACUMN TESTS. ENGINEER ON RECORD 3RD PARTY ENGINEER TO VERIFY MAN HOLE 3 AND 4 TESTS AND PRESSURE TEST ENTIRE SYSTEM. PENDING VERIFICATION FROM 3RD PARTY ENGINEERING. |