Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2021 | MECHANICAL - FINAL | Approved | ||
| 03/16/2021 | MECHANICAL - FINAL | Partial Approval | Partial approval Need p-trap on gas pack on roof and approved manual j Please replace/repair disconnect at unit and mark heat strips installed in unit on unit data tag and verify proper fusses are installed Please install GFI on roof |
|
| 03/12/2021 | MECHANICAL - FINAL | Cancelled | CANCELLED BY CONTRACTOR |