Permit: T17CM06999

Parcel: 138230950


Addresses:

701 W CALLE ARAGON

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/28/2019 MECHANICAL - FINAL Approved
11/05/2018 MECHANICAL - FINAL Denied Protect all exposed Romex from physical damage in bedroom closet
see letterhead from energy source electrical dated 8/16/18
missing dead front sub panel
label all circuits
schedule all open inspections
08/21/2018 MECHANICAL - FINAL Partial Approval PA for Evap cooler on roof. Upon completeion of missing permanent room heat source and branch circuit inspection (wiring/Breaker) then the Final Mechanical can be inspected for compliance.