Permit: T17CM06911

Parcel: 138210330


Addresses:

270 W TETON ST

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
12/21/2017 EXCAVATION/LAYOUT REBAR & ZON Approved
12/18/2017 EXCAVATION/LAYOUT REBAR & ZON Denied COVERED W/O INSPECTION
11/22/2017 EXCAVATION/LAYOUT REBAR & ZON Denied PLAN CALLS FOR 2X10 RAFTERS 2X8'S INSTALLED
MISSING OUTLETS PER PLAN
EXPOSE FOOTERS TO VERIFY DEPTH PER PLAN
EXPOSE RAFTER TO WALL CONNECTIONS
PLAN CALLS FOR 2X6 WALL FRAMING 2X4 INSTALLED
EXPOSE DUCT WORK PER PLAN
WATER HEATER B-VENT NOT TO CODE
COMPLY WITH PREVIOUS
11/21/2017 EXCAVATION/LAYOUT REBAR & ZON Denied PROVIDE ACCESS
PROVIDE APPROVED PLANS
EXPOSE ALL WORK TO PLAN FOR INSPECTION OR PROVIDE LETTERHEAD FROM LICENSED GENERAL CONTRACTOR STATING ALL WORK TO PLAN DONE TO CODE FOR SAFETY