Inspection Status: Partial Approval
Inspection History: FIRE - FINAL
Permit Number - T17CM06768
Inspection Description - FIRE - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2018 | FIRE - FINAL | Partial Approval | PA pending building approval on my notes. 1) Cover sheet show OL of 50 with seating (48) and service area (2), which would require two exits. Sheet A-3 shows seating area as 640sqft which equals 43 OL and 352 sqft for service area which equals 2 OL. Total of 45 OL from sheet A-3 sqft information. You may be required to change OL numbers on cover sheet. Per numbers from A3, one exit is OK. |
|
04/24/2018 | FIRE - FINAL | Approved | ||
04/23/2018 | FIRE - FINAL | Denied | NOT READY Fire alarm not connected Need "gas valve" sign on ceiling tile Fire sprinkler heads are taped/painted Need fire sprinkler and fire alarm final pay re-inspection fees |
|
04/20/2018 | FIRE - FINAL | Denied | DENIED. Not ready. -Allan fire did not call in their permit. -Sprinkler plans not on site. Sprinkler inspection not conducted. -Hood company not on site for acceptance test. -Hood not interconnected to fire alarm panel per the PM and super. -Alarm company not on site to verify signals. -Need all inspections approved/finaled. -Need operational permit for "places of assembly." -Reinspection fee added. Must be paid prior to final. -Will verify CO2 quantities at final. -Will verify the one exit requirement with Eric from bldg dept. |