Permit: T17CM06631

Parcel: 111060280


Addresses:

2950 N DODGE BL #4

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
09/11/2017 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
09/07/2017 MECHANICAL - INTERMEDIATE Partial Approval MINI SPLIT CONDENSOR OVERFUSED.
PROVIDE HOSE CLAMP ON CONDENSATE PUMP.
MARK FAN COIL DATA PLATE WITH HEAT STRIP AND FUSE ACCORDINGLY.
VINYL DRAIN HOSE NOT LISTED FOR OUTDOOR.
USE.
COAT ALL EXPOSED ARMAFLEX.
PROVIDE TAMPER PROOF CAPS AT CONDENSOR.
TERMINATE CONDENSATE DRAINS WITH AN ELBOW AND SHORT NIPPLE.
NEED TO SEE 2" DUCT LINER IN EXPOSED DUCT ON ROOF.
09/06/2017 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*