Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2017 | PLUMBING - INTERMEDIATE | Approved | ||
| 08/30/2017 | PLUMBING - INTERMEDIATE | Denied | 1- SHALL REMOVE THE FERNCO COUPLING UNDER THE SLAB AND PROVIDE THE REQUIRED MISSION SPECILATY COUPLING. 2- SHALL PROVIDE A AIR PRESSURE TEST ON UNDERGROUND ROUGH PLUMBING (5) PSI MINIMUM. 3- SHALL PROVIDE THE REQUIRED NAIL PLATE ON SOLE PLATE AT LAVATORY RISER. 4- TRAP ARMS FOR THE DOUBLE LAVATORY CAN NOT HAVE ANY VERTICAL OFFSETS. THIS PLACES THE WEIR OF THE TRAP ABOVE THE OUTLET OF THE VENT. 5- SHALL REMOVE THE JIM TEST CAP IN WALL AND PROVIDE A APPROVED PERMANETE CAP. |