Permit: T17CM06616

Parcel: 133100900


Addresses:

8610 E BELLEVUE PL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/05/2017 PLUMBING - ROUGH, SOIL Approved
08/30/2017 PLUMBING - ROUGH, SOIL Denied 1- SHALL REMOVE THE FERNCO COUPLING UNDER THE SLAB AND PROVIDE THE REQUIRED MISSION SPECILATY COUPLING.
2- SHALL PROVIDE A AIR PRESSURE TEST ON UNDERGROUND ROUGH PLUMBING (5) PSI MINIMUM.
3- SHALL PROVIDE THE REQUIRED NAIL PLATE ON SOLE PLATE AT LAVATORY RISER.
4- TRAP ARMS FOR THE DOUBLE LAVATORY CAN NOT HAVE ANY VERTICAL OFFSETS. THIS PLACES THE WEIR OF THE TRAP ABOVE THE OUTLET OF THE VENT.
5- SHALL REMOVE THE JIM TEST CAP IN WALL AND PROVIDE A APPROVED PERMANETE CAP.