Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2017 | PLUMBING - FINAL | Approved | OK COMM. GAS | |
| 10/04/2017 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/08/2017 | PLUMBING - FINAL | Denied | PROVIDE 3" DOUBLE WALL VENT FOR EXISTING WATER HEATER WITH MIN. 1" CLEARANCE FROM COMBUSTIBLES. EXTEND VENT 2' ABOVE PARAPET. PROVIDE A SEDIMENT TRAP. INSTALL NEW WATER HEATER AND EXTEND VENT 3' ABOVE EVAP COOLER. |
|
| 09/07/2017 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 * |