Permit: T17CM06597

Parcel: 124121060


Addresses:

1221 E MILES ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
11/22/2017 MECHANICAL - INTERMEDIATE Approved
11/21/2017 MECHANICAL - INTERMEDIATE Denied boxs framed 3 sides, insulate branch fittings, PVC over stressed at 90
11/16/2017 MECHANICAL - INTERMEDIATE Not ready for Inspection branch fittings to be insulated to minimum R-8
duct drops to be insulated to minimum R-8
all PVC joints and fittings to be primed prior to glue, primer is to be purple in color