Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T17CM06577
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2017 | PLUMBING - INTERMEDIATE | Approved | ||
12/11/2017 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE A 2 INCH WASTE LINES FOR THE SECOND FLOOR MASTER BATH LAVATORYS AND CONNECT THEM TO THE GRAY WATER SYSTEM. 2- CAN NOT CONNECT THE 2 INCH LAVATORY WASTE LINE INTO THE CLOSET BEND FOR THE SECOND FLOOR BATH #2. 3- SHALL PROVIDE A 2 INCH CLEAN OUT AT WASTE STACK IN GARAGE. 4- RETEST THE SYSTEM. * |
|
12/08/2017 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 * |
|
12/05/2017 | PLUMBING - INTERMEDIATE | Partial Approval | ||
12/05/2017 | PLUMBING - INTERMEDIATE | Partial Approval | SUPPORT HORIZONTAL ABS EVERY 4 FT SECURE PEX HORIZONTAL EVERY 32 INCHES SECURE CLOSET RING FILL TUB TO OVERFLOW |
|
12/04/2017 | PLUMBING - INTERMEDIATE | Cancelled |