Permit: T17CM06390

Parcel: 117083960


Addresses:

870 S 10TH AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/10/2018 BUILDING - FINAL Approved
04/02/2018 BUILDING - FINAL Denied PROVIDE BOND BUSHING AT ALL CONDUITS ENTERING AND EXITING BOXES AND METER CAN.
BODY GROUNDS MUST HAVE PAINT REMOVED BEHIND FOR FULL CONTACT.
SECURE WIRING TO RACK ON ROOF. (LEAVE NOTHING DANGELING).
PROVIDE REVISION FOR CHANGE OF PANEL LAYOUT.