Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2017 | ELECTRIC - FINAL | Approved | CLEAR ELECTRIC RECN. | |
| 08/16/2017 | ELECTRIC - FINAL | Denied | 1- THE GROUND UFER HAS BEEN CUT. SHALL LAND THE UFER GROUNDING CONDUCTOR AS PER SECTION 250.64 (C) 2011 NEC. 2- SHALL EXTEND THE RISER MAST 8 FEET ABOVE THE ROOF AS PER SECTION 230.24 (A) 2011 NEC. OR PROVIDE THE REQUIRED CLEARANCES FROM TEP UTILITY PROVIDER. |