Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/04/2018 |
MECHANICAL - FINAL |
|
Approved |
APPROVED WITH R SHERRY'S APPROVAL OF AIR BALANCE REPORT |
| 05/30/2018 |
MECHANICAL - FINAL |
|
Partial Approval |
REVIEW OF AIR BALANCE REPORT COMPLETED |
| 05/22/2018 |
MECHANICAL - FINAL |
|
Denied |
BALANCE REPORT INDICATES INADEQUATE MAKE UP AIR OR EXCESSIVE EXHAUST FOR THE BUILDING. CONTACT ENGINEER. REFERENCE: SECTION 508.1, IMC 2012. |