Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T17CM06264

Parcel: 131132550

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/04/2018 MECHANICAL - FINAL Approved APPROVED WITH R SHERRY'S APPROVAL OF AIR BALANCE REPORT
05/30/2018 MECHANICAL - FINAL Partial Approval REVIEW OF AIR BALANCE REPORT COMPLETED
05/22/2018 MECHANICAL - FINAL Denied BALANCE REPORT INDICATES INADEQUATE MAKE UP AIR OR EXCESSIVE EXHAUST FOR THE BUILDING. CONTACT ENGINEER. REFERENCE: SECTION 508.1, IMC 2012.