Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2018 | ELECTRIC - UFER | Approved | ||
| 01/09/2018 | ELECTRIC - UFER | Denied | UFER MUST BE ATTACHED TO A MINIMUM 20' REBAR, IN THE BOTTOM 1/3 OF THE FOOTING. NOT ON SLAB REBAR. RELOCATE AND RECALL |