Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM06198
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/26/2017 | FIRE - FINAL | Approved | C of O may be given for 20th floor. Items to be followed up with CBRE. -Stairwell pressurization -Atrium smoke control -Printer for Fire Alarm -"Fire Command Room" label -Copy of Annual Fire Alarm Inspection |
|
12/21/2017 | FIRE - FINAL | Partial Approval | General Contractor: Exit lights need to read "EXIT" only "TIXE" needs to be covered with covering listed with light Fire extinguisher cabinets need to read " pull here" with arrow pointing in direction and or "open here" with arrow pointing in direction Escutcheon located West elevator lobby doors needs to be replaced and or cleaned Electrical panels need to be labeled, breakers numbered and panel names defined Exit sign on the elevator lobby doors needs to be removed (2) Elevator light signs need to be covered/ replaced Open electrical J boxes need to be covered A temporary certificate of occupancy will be issued for the loading of furniture only and not occupants until December 27th at 4:00 p.m. Fire alarm issues must be resolved and tested prior to the authorization of C of O. Fire alarm issues: Smoke detector 20th floor server room is within 3' of the air needs to be relocated to meet code Provide documentation regarding the audibility/intelligibility test has been performed Breaker for the power supply 24th floor ELP-24 CKT 1 needs to be red as required by NFPA 70 Electrical panel schedule needs to reflect that Crkt 1 is the FAPS and not telco Confirm that the fire alarm is sending alarm, trouble and supervisory signals off-site Confirm the stairwell pressurization is kicking on Confirm that the atrium smoke control is kicking on Confirm the elevator recall protocol Confirm fire alarm activation on 20th floor with water flow Other building issues (CBRE Responsibility): Fire alarm has multiple troubles on it that shall be repaired prior to obtaining C of O for 20th floor Printer for the fire alarm system is not operating Door to FACP needs a sign that reads "Fire Command Room" Fire alarm communicators that are obsolete shall be removed from the system Electrical panel 24th floor needs to be properly labeled and locked out regarding fire alarm, booster panels and applicable amplifiers Provide current copy of the fire alarm inspection report |
|
12/20/2017 | FIRE - FINAL | Denied | 1. Unable to reach 20th floor without clearance. |