Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2017 | PLUMBING - GAS PRESSURE TEST | Approved | CLEAR GAS METER | |
| 08/18/2017 | PLUMBING - GAS PRESSURE TEST | Denied | 1- SHALL BOND THE GAS LINE #6 GROUND CONDUCTOR. 2- SHALL REMOVE THE MECHANICAL TAPE AROUND THE DOUBLE WALL FLU VENT FOR THE WATER HEATER AND PROVIDE (3) SHEET METAL SCREWS PER JOINT AND ON THE DRAFT COLLAR. 3- SHALL REMOVE THE FLEX CONNECTORS ON THE WATER HEATER T & P DRAIN. 4- SHALL SEAL THE GAS LINE PENETRATION THRU THE EXTERIOR WALL BY METER. 5- SHALL PROVIDE A CARBON MONOXCIDE DETECTOR. 6- SHALL CONNECT THE DRYER VENT. 7- SHALL PROVIDE COMBUSTION AIR VENTS FOR WATER HEATER. |