Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2017 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/03/2017 | MECHANICAL - INTERMEDIATE | Denied | Condensate pipe is out of the wall, joints were not primed, and are under strain, improperly used metal conduit clamps have been used on pvc. Install PVC per min standards with code approved supports and methods. TPR not installed. Provide proper drainage fittings on DWV system at vent connections and revents, also below fixture flood level. Secure pex, protect from sharp edges. * |
|
| 11/02/2017 | MECHANICAL - INTERMEDIATE | Partial Approval | SEAL BATHROOM EXHAUST ROOF PENETRATIONS |