Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2020 | ELECTRIC - INTERMEDIATE | Approved | ||
| 12/21/2018 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | no wiring for water heater. Still need to use correct boxes or extensions on exterior boxes. Previously used box for a smoke alarm in middle bedroom cannot be covered up by sheet rock bring down to ceiling level and use as junction box. Still missing exterior receptacle by front door. Another failed inspection will result in a reinspection fee. | |
| 12/14/2018 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | repair Romex in master closet and staple within 6 inches of box. Need correct boxes or extensions on exterior boxes. Need fridge on dedicated circuit. Need exterior receptacle by front door. Need smoke alarm boxes is at correct heights. Smoke alarm in the middle bedroom too close to supply air. Another failed inspection may result in a reinspection fee. | |
| 10/04/2018 | ELECTRIC - INTERMEDIATE | Denied | Verify 2:20 amp small appliance circuits kitchen counters provide dedicated refrigerator Outlet secure home runs nail protector throughout seal top plate penetrations stopped inspection too many items to list |