Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 02/21/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
OK to clear electric INCR. Need 2 ground rods installed 6 foot apart (existing ground OK only to get power turned back on) need address label. Need gas and water bonded. Need panel labeled, if breakers are not used they need to be blanked out. Need to repair stucco behind and around panel. |