Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2017 | MECHANICAL - FINAL | Approved | ||
| 08/18/2017 | MECHANICAL - FINAL | Denied | PROVIDE MIN. 2" - R8 DUCTLINER. 1" WAS USED. PROVIDE AN APPROVED COUPLING IN GAS LINE, NOT A THREAD PROTECTOR. |
|
| 08/17/2017 | MECHANICAL - FINAL | Denied | NO ACCESS TO ROOF. | |