Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/26/2017 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 09/15/2017 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
tandem breakers cannot be used on molti-wire circuit. |
| 09/07/2017 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
I.D. all breakers, expose top' of ground rods, note; tandem breakers cannot be used on molti-wire circuits, it can overload neutrals |
| 09/01/2017 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
Per Bruce S. Ok for temp. Incr. clearance. Contractor to provide and install correct breaker/panel that will work for this backfeed situation. |