Permit: T17CM05856

Parcel: 12310001A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T17CM05856

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/07/2019 ELECTRIC - INTERMEDIATE Approved
01/23/2019 ELECTRIC - INTERMEDIATE Partial Approval Installation of new switch gear #S3N-B05 (277-480), S1C-B02 (120-208); new transformer #TR1C-B0T. OK to energize equipment
07/23/2018 ELECTRIC - INTERMEDIATE Partial Approval TRANSFORMER AND MAIN BREAKER #S1N-BO5; BUSS DUCT #S1-BO5. OK TO ENERGIZE EQUIPMENT.
05/08/2018 ELECTRIC - INTERMEDIATE Partial Approval SWITCH GEAR #4 OF 5 AND #5 OF 5. ALL LINES TORQUED AS PER SPECIFICATIONS. OK TO ENERGIZE SYSTEM.
12/19/2017 ELECTRIC - INTERMEDIATE Partial Approval ELECTRIC VAULT PLACE IN SOUTH EAST CORNER OF BUILDING; CONDUIT LINES (4" @2, 5" @3) EAST AND WEST OF VAULT. OK TO PLACE CONCRETE.