Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T17CM05856
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2019 | ELECTRIC - INTERMEDIATE | Approved | ||
01/23/2019 | ELECTRIC - INTERMEDIATE | Partial Approval | Installation of new switch gear #S3N-B05 (277-480), S1C-B02 (120-208); new transformer #TR1C-B0T. OK to energize equipment | |
07/23/2018 | ELECTRIC - INTERMEDIATE | Partial Approval | TRANSFORMER AND MAIN BREAKER #S1N-BO5; BUSS DUCT #S1-BO5. OK TO ENERGIZE EQUIPMENT. | |
05/08/2018 | ELECTRIC - INTERMEDIATE | Partial Approval | SWITCH GEAR #4 OF 5 AND #5 OF 5. ALL LINES TORQUED AS PER SPECIFICATIONS. OK TO ENERGIZE SYSTEM. | |
12/19/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | ELECTRIC VAULT PLACE IN SOUTH EAST CORNER OF BUILDING; CONDUIT LINES (4" @2, 5" @3) EAST AND WEST OF VAULT. OK TO PLACE CONCRETE. |