Permit: T17CM05768

Parcel: 13413057N

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM05768

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2018 FIRE - FINAL Approved Mag doors are fail safe on power loss.
Mag door unlock immediately on water flow alarm and smoke detection in corridor of wing.
07/24/2018 FIRE - FINAL Partial Approval 1) Add chevron to exit sign next to activity room door, or remove exit sign, or relocate sign. Can also choose to change keyed lockset to nonkeyed.
2) Mag locks on exit doors shall release on power loss.