Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2018 | FIRE - FINAL | Approved | Mag doors are fail safe on power loss. Mag door unlock immediately on water flow alarm and smoke detection in corridor of wing. |
|
| 07/24/2018 | FIRE - FINAL | Partial Approval | 1) Add chevron to exit sign next to activity room door, or remove exit sign, or relocate sign. Can also choose to change keyed lockset to nonkeyed. 2) Mag locks on exit doors shall release on power loss. |