Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T17CM05657
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2017 | BUILDING PRE-SLAB | Approved | ||
08/25/2017 | BUILDING PRE-SLAB | Denied | 1- STEEL REINFORCEMENT AT EAST FOOTING IS NOT TIED DOWN. 2- UFER IS ON THE BOTTOM OF THE FOOTING. 2 INCHES MINIMUM OF CONCRETE BELOW THE UFER IS REQUIRED. |