Permit: T17CM05609

Parcel: 137054810


Addresses:

5158 S 17TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/18/2017 ELECTRIC - SERVICE UPGRADE Approved INC
CONTACTED MIKE (TEP)
08/17/2017 ELECTRIC - SERVICE UPGRADE Denied SECURE HUB AT SERVICE ENTRANCE
PROVIDE RISER CLAMPS
IDENTIFY NEUTRAL
08/14/2017 ELECTRIC - SERVICE UPGRADE Denied SECURE PANEL WITH MIN 1/4' SCREWS OR BOLTS
LOWER PANEL TO MIN 6'-8" TO HIGHEST BREAKER
CONTINOUS #4 GROUND TO BOTH GROUND RODS TO GROUND BUSS
ATTACH BOND WIRE TO GROUND BUSS
PROVIDE CLAMPS AT RISER
08/11/2017 ELECTRIC - SERVICE UPGRADE Not ready for Inspection 1- provide 2 ground rods 8' in length, 6' apart #4 bond wire
2- bond gas and water
3- blank open KO at panel
4- provide roof jack at riser