Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2017 | ELECTRIC - SERVICE UPGRADE | Approved | INC CONTACTED MIKE (TEP) |
|
| 08/17/2017 | ELECTRIC - SERVICE UPGRADE | Denied | SECURE HUB AT SERVICE ENTRANCE PROVIDE RISER CLAMPS IDENTIFY NEUTRAL |
|
| 08/14/2017 | ELECTRIC - SERVICE UPGRADE | Denied | SECURE PANEL WITH MIN 1/4' SCREWS OR BOLTS LOWER PANEL TO MIN 6'-8" TO HIGHEST BREAKER CONTINOUS #4 GROUND TO BOTH GROUND RODS TO GROUND BUSS ATTACH BOND WIRE TO GROUND BUSS PROVIDE CLAMPS AT RISER |
|
| 08/11/2017 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | 1- provide 2 ground rods 8' in length, 6' apart #4 bond wire 2- bond gas and water 3- blank open KO at panel 4- provide roof jack at riser |