Inspection History: FIRE - FINAL
Permit Number - T17CM05449
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2017 | FIRE - FINAL | Approved | ||
09/29/2017 | FIRE - FINAL | Denied | Need separate fire alarm permit for all smoke alarm replacements. We need to test every new smoke. Will also verify escutcheons on reinspection. | |
08/31/2017 | FIRE - FINAL | Denied | 1. Same notes as 8/30/2017. | |
08/30/2017 | FIRE - FINAL | Denied | 1. Need corridor smokes, exit pathways, and lighting complete prior to occupying. | |
08/01/2017 | FIRE - FINAL | Partial Approval | Ok to hardlid Phase 2 hallway. Verified fire caulking above ceiling. | |
07/24/2017 | FIRE - FINAL | Partial Approval | Ok to hardlid Phase 1 hallway. Verified fire caulking above ceiling. |