Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T17CM05287
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2018 | PLUMBING - FINAL | Approved | ||
04/04/2018 | PLUMBING - FINAL | Partial Approval | REVIEW OF WATER CHLORINATION REPORT COMPLETED | |
04/04/2018 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE A 1022 IN LINE BACKFLOW PREVENTERS FOR ALL ICE MAKERS AND TEA DISPENSER MACHINE. 2- SHALL PROVIDE A SAFTEY CABLE FOR THE OVEN. 3- SHALL REMOVE THE FERNCO COUPLING ON THE TRIPPLE COMPARTMENT SINK INDIRECT WASTE LINE. 4- SHALL PROVIDE VACUUM BREAKERS ON ALL EXTERIOR HOSE BIBS. 5- SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT ON THE WATER HEATER FLU VENT AND DRAFT COLLAR. 6-SHALL PROVIDE A MINIMUM OF 1 INCH ANULAR SPACE AROUND THE WATER HEATER FLU VENT THU THE CEILING. 7- SHALL LOCATE THE ACCESSIBLE RESTROOMS MIRROR 40 INCHES FROM FLOOR LEVEL TO THE REFLECTION OF THE MIRROR. 8- SHALL PROVIDE A PERMANATE LABLE SHOWING THE ANZUL VALVE LOCATION ON THE CEILING TILE. * |
|
10/26/2017 | PLUMBING - FINAL | Prior to Final Inspectn | WATER CHLORINATION REPORT REQUIRED |