Permit: T17CM05142

Parcel: 133130490


Addresses:

7822 E ELIDA ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/12/2018 FRAMING Approved
01/11/2018 FRAMING Partial Approval IVRS - Inspection :*
1- SHAll SEAL ALL TOP PLATE PENETRATIONS WITH FIRE RATED FOAM OR CAULKING.
2- SHALL PROVIDE A GAS LINE BTU TO CFH DEMAND FOR THE ADDED BBQ GAS SUPPLY.
3- SHALL PROVIDE THE REQUIRED GAS PRESSURE TEST GAGE OF 15 LBS WITH 1/10TH INCREMENTS.
4- SHALL LOCATE THE HORIZONTAL VENT FOR THE KITCHEN SINK A MINIMUM OF 6 INCHES ABOVE THE FLOOD LEVEVL RIM OF THE FIXTURE.
5- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM TO TOP OF VENT.