Permit: T17CM05090

Parcel: 115044540


Addresses:

1135 N PARK AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T17CM05090

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/29/2018 ELECTRIC - INTERMEDIATE Approved
10/26/2017 ELECTRIC - INTERMEDIATE Partial Approval PASS-THROUGH WALL OK TO DRYWALL
10/09/2017 ELECTRIC - INTERMEDIATE Denied NON- METALLIC CONNECTORS ARE BEING USED ON MC CABLE.
MC CABLE IS BEING RUN TO PLASTIC BOXES.
MC CABLE AND ROMEX WIRING ARE CONCEALED IN THE WALLS AND CEILINGS. I WAS TOLD BY THE OWNER THAT THERE WAS A LICENSED ELECTRICIAN DOING THE WORK, HOWEVER, HE COULDN'T GIVE ME THE CONTRACTORS NAME.
NEW SERVICE UPGRADE ON NORTH SIDE OF BUILDING.