Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2018 | MECHANICAL - HOODS | Approved | ||
| 06/27/2018 | MECHANICAL - HOODS | Denied | LABEL ALL ELECTRICAL PANELS SECURE KITCHEN EXHAUST FAN TO CURB ATTACH EXHAUST FAN GREASE TRAY PAINT ABS PIPES ON ROOF LABEL DISCONNECTS ON ROOF BOND GAS AND WATER TO GROUND GFCI RECEPTACLES REQUIRED 6' FROM ALL SINKS WRAP COPPER PIPES ON ROOF INCORRECT LIGHTING IN COOLER, CONDENSATION IN FIXTURE. STOP INSPECTION. |
|
| 06/20/2018 | MECHANICAL - HOODS | Not ready for Inspection | NEED FIRE HOOD INSPECTIONS COMPLETED. | |
| 03/27/2018 | MECHANICAL - HOODS | Partial Approval | NEEDS CONTAINMENT TEST. | |
| 03/09/2018 | MECHANICAL - HOODS | Partial Approval | DUCT WARPPED | |
| 03/07/2018 | MECHANICAL - HOODS | Partial Approval | SMOKE TEST ON HOOD DUCT |