Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2017 | MECHANICAL - FINAL | Approved | ||
| 07/25/2017 | MECHANICAL - FINAL | Denied | DOUBLE WALL VENT REQUIRES MIN. 1' FROM COMBUSTIBLES. THIS INCLUDES THE TAR TAPE AND DOOR JAMB. THE 1ST FITTING AT FURNACE IS UPSIDE DOWN. YOU CANNOT USE A SINGLE WALL FITTING TO SPLICE 2 PIECES OF DOUBLE WALL VENTS. AMERIVENT AND DURA VENT DO NOT HAVE MATCHING ENDS. |
|
| 07/12/2017 | MECHANICAL - FINAL | Partial Approval | CORRECTIONS HAVE NOT BEEN MADE. | |