Permit: T17CM05025

Parcel: 133133690


Addresses:

7557 E BOOKMARK PL


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T17CM05025

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2017 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
09/22/2017 MECHANICAL - INTERMEDIATE Denied 1- SHALL PROVIDE (3) SIDED BLOCKING AT ALL FORCED AIR VENTS.
2- SHALL SEAL ALL TOP PLATE PENETRATIONS WITH FIRE RATED FOAM OR CAULK.
3- SHALL SECURE THE GAS LINE.
4- SHALL PROVIDE A WATER TEST ON DWV SYSTEM.