Permit: T17CM04990

Parcel: 12603177A


Addresses:

601 N SWAN RD

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/30/2017 PLUMBING - FINAL Denied 1- SHALL PROVIDE A SHEET METAL CAP FOR THE UNUSED OPENING ON THE FURNACE AND WATER HEATER FLU VENT. MECHANICAL TAPE IS NOT ACCEPTED.
2- SHALL STRAP AND SUPPORT THE GAS RISER ON ROOF FOR THE GAS PACK IN A APPROVED METHOD.
3- CALL FOR FINAL INSPECTION WHEN CORRECTIONS ARE COMPLETE.