Permit: T17CM04954

Parcel: 111080640

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/01/2017 ELECTRIC - FINAL Approved
07/28/2017 ELECTRIC - FINAL Denied OPEN EXTERIOR WALL IN CLOSET TO SEE BOTTOM PLATE.
ALL METAL BOXES TO HAVE ROMEX CONNECTORS.
07/20/2017 ELECTRIC - FINAL Denied PROVIDE ARC FAULT BREAKERS AND TAMPER PROOF RECEPTACLES.
PROVIDE ROMEX CONNECTORS AT JBOXES IN ATTIC.
PROVIDE TREATED WOOD AT EXTERIOR BOTTOM PLATES.
EXPOSE ELEC. AT 2 BOXES IN EACH ROOM.
PROVIDE 3 PRONG RECEPTACLES.PROVIDE GROUNDING JUMPERS AT ALL METAL BOXES.