Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM04835
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2017 | FIRE - FINAL | Approved | ||
09/21/2017 | FIRE - FINAL | Denied | 1) Sprinkler heads in front sales area too far off wall, 9'4" 2) Need 12" address numbers on bldg. 3) Add suite numbers to rear door. 4) Remove one of the locks off front exit door. Cannot have panic hardware and quarter turn lock. Panic not required. 5) Reparir or remove all emergency lights and exit signs. Not required but if you have they must work. |
|
09/19/2017 | FIRE - FINAL | Denied | DENIED -Nobody on site, No access, No message. -Reinspection fee x 2 added to permit for multiple fire final inspections. Must be paid prior to next fire inspection. -See comments from previous inspector for inspection notes. Also did not notice an address on building or suite. Suite number on rear door needs to be verified. |
|
09/15/2017 | FIRE - FINAL | Denied | Need power on to test emergency lights, exit signs, and verify fire alarm functions. Mount fire extinguishers. |