Permit: T17CM04835

Parcel: 13734001D

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM04835

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2017 FIRE - FINAL Approved
09/21/2017 FIRE - FINAL Denied 1) Sprinkler heads in front sales area too far off wall, 9'4"
2) Need 12" address numbers on bldg.
3) Add suite numbers to rear door.
4) Remove one of the locks off front exit door. Cannot have panic hardware and quarter turn lock. Panic not required.
5) Reparir or remove all emergency lights and exit signs. Not required but if you have they must work.
09/19/2017 FIRE - FINAL Denied DENIED
-Nobody on site, No access, No message.
-Reinspection fee x 2 added to permit for multiple fire final inspections. Must be paid prior to next fire inspection.
-See comments from previous inspector for inspection notes. Also did not notice an address on building or suite. Suite number on rear door needs to be verified.
09/15/2017 FIRE - FINAL Denied Need power on to test emergency lights, exit signs, and verify fire alarm functions. Mount fire extinguishers.