Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2017 | BUILDING - PROGRESS | Approved | ||
| 07/04/2017 | BUILDING - PROGRESS | Denied | THIS SERVICE DOES NOT HAVE A GROUNDING ELECTRODE SYSTEM. PROVIDE 2 - 8' GROUNDS MIN. 6' APART AND CONNECT TO SERVICE EQUIPMENT. |