Permit: T17CM04788

Parcel: 134210550


Addresses:

223 S BIRCH PL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/31/2018 PLUMBING - ROUGH, SOIL Approved Green #18 tracer wire up out of dirt at each end and run along pipe in ditch is required at buildin drain to short sewer line connection in yard.
All coper to Galvanized connections to be brass fittings or nipples or dielectric fittings.
07/26/2018 PLUMBING - ROUGH, SOIL Correction Required Vent take offs to be above centerline of pipe or 45 degreesfrom level. Foam sleeve or wrap all water lines below grade with required/approved foam insulation. All 2" drain lines to have 1/4" per foot slope towards the building drain. All--Copper to Galvanized pipe connections shall be separated with a Brass nipple or approved dielectric fitting to prevent oxidation reduction (electrolisis/decomposition) of the pipes .
There shold be a 10 foot high secured ABS pipe that fills the complete DWV system to pressure test the system for leaks.
07/23/2018 PLUMBING - ROUGH, SOIL Not ready for Inspection