Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 08/02/2018 |
ELECTRIC - UFER |
|
Approved |
|
| 07/31/2018 |
ELECTRIC - UFER |
|
Not ready for Inspection |
minimum 2 8 foot ground rods a minimum of 6 feet apary required. You may also put a UFER grond in the foundation and attach the min 20 foot below grade bar to the bottom steel in the footing. add a few feet in order to bend the bar vertically for GEC attachment later. |