Permit: T17CM04771

Parcel: 117110980


Addresses:

37 E PENNINGTON ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T17CM04771

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2018 MECHANICAL - FINAL Approved
03/05/2018 MECHANICAL - FINAL Partial Approval REVIEW OF AIR BALANCE REPORT COMPLETE
02/26/2018 MECHANICAL - FINAL Not ready for Inspection no work
02/22/2018 MECHANICAL - FINAL Not ready for Inspection provide access to AHU units
revise plans to show changes
copper line sets in contact with galv.
provide approved filter size
pending air balance approval
provide secondary drains at AHU
provide U.V. protection at line sets
provide clearence from VTR to OSA inlets
02/21/2018 MECHANICAL - FINAL Denied THE MECHANICAL SYSTEM HAS NOT BEEN ISTALLED PER THE APPROVED PLANS. RESUBMIT THE BALANCE REPORT AFTER THE PLANS HAVE BEEN REVISED.