Permit: T17CM04695

Parcel: 111052580

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T17CM04695

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2017 FRAMING Approved IVRS - Inspection :*
09/15/2017 FRAMING Denied 1- NO ACCESS TO UNIT 227,DOOR WAS LOCKED.
2- SHALL PROVIDE A BRASS PLUG FOR UNUSED DRAIN, PLASTIC PLUG NOT APPROVED FOR CAST IRON.
3- SHALL NOT REDUCE THE LAVATORY DRAIN FROM 2 INCH TO 1 1/2 INCH.
3- SHALL LOCATE THE HORIZONTAL REVENT A MINIMUM OF 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE FIXTURE,
5- SHALL PROVIDE MISSION SPECIALTY COUPLING WHEN CON NECTING DISSIMULAR MATERIALS ON THE SANITARY WASTE AND VENT SYSTEM.
09/11/2017 FRAMING Denied 1- SEE NOTE #1.
2- LAVATORY TRAP ARM DOES NOT MEET CODE.
3- SHALL REMOVE ALL SWITCHES AND OUTLETS IN ORDER TO VERIFY THAT ALL METAL BOXES HAVE BEEN GROUNDED.
4- SHALL PROVIDE A CONDUCTOR STAPLE WITHIN 6 INCHES OF THE GANG BOX ON IN HALLWAY.
09/07/2017 FRAMING Cancelled IVRS - RI canceled
07/26/2017 FRAMING Denied 1- SHALL SEAL ALL TOP PLATE PENETRATIONS WITH FIRE RATED CAULK OR FOAM.
2- SHALL REPAIR ALL TEARS ON HVAC FLEX DUCTS.
3- SHALL SECURE THE 1ST FLOOR BATHROOM LIGHT BOX.