Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T17CM04651
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2017 | PLUMBING - INTERMEDIATE | Approved | ||
06/21/2017 | PLUMBING - INTERMEDIATE | Denied | secure tubing in walls Provide 18 inches of copper from sweat connections at wh flex and sov and PEX tubing per MII or install iron pipe adaptor for those connections. |
|
06/20/2017 | PLUMBING - INTERMEDIATE | Partial Approval | UNITS 1507, 1508, 1517, 1518, 1527, 1528 ARE OK FOR PATCHING. | |
06/19/2017 | PLUMBING - INTERMEDIATE | Partial Approval | 1- OVERHEAD AND IN WALL DOMESTIC WATER DISTRIBUTION IS OKAY FOR SHEET ROCK PATCH IN UNITS 1505,1506,1515,1516,1525,1526 ONLY. | |
06/16/2017 | PLUMBING - INTERMEDIATE | Partial Approval | 1- OVERHEAD AND IN WALL DOMESTIC WATER DISTRIBUTION IS OKAY FOR SHEET ROCK PATCH IN UNITS 1503,1504,1511,1521,1512,1522,1513,1523,1514,1524 ONLY. |