Permit: T17CM04586

Parcel: 12810079B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM04586

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2017 FIRE - FINAL Approved Note: Big A Fans need to be connected but they need a new data base for the fire alarm. Since this will take a few days-weeks I advised that they can open full C of O and just do not trun on the fans until they are connected and tested. Fire alarm permit will remain open until connected.
08/04/2017 FIRE - FINAL Partial Approval TCO for soft opening - ok to occupy for soft openeing. Hood, alarm, and fire final still needed prior to hard opening.
07/31/2017 FIRE - FINAL Denied Need fire alarm, fire sprinkler permits and work approved. Kitchen system needs the final trip, heads in both outside areas are painted and need to be replaced, mount, tag and sign fire extinguishers, replace missing esutcheons, electrical panels need schedules and labels. Provide a current copy of the fire alarm and fire sprinkler reports.