Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T17CM04586
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2017 | FIRE - ALARM FINAL | Approved | Big A Fans need to be connected but they need a new data base for the fire alarm. Since this will take a few days-weeks I advised that they can open full C of O and just do not trun on the fans until they are connected and tested. Fire alarm permit will remain open until connected. | |
08/08/2017 | FIRE - ALARM FINAL | Partial Approval | Note: Big A Fans need to be connected but they need a new data base for the fire alarm. Since this will take a few days-weeks I advised that they can open full C of O and just do not trun on the fans until they are connected and tested. | |
08/04/2017 | FIRE - ALARM FINAL | Partial Approval | Temp C of O ok for soft opening only. FA needs to verify that big fans shut down upon alarm event. | |
07/31/2017 | FIRE - ALARM FINAL | Denied | Needs plan and permit (B.A.F.) shut down, shut down the music |