Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/09/2017 |
FIRE - ALARM FINAL |
|
Approved |
Big A Fans need to be connected but they need a new data base for the fire alarm. Since this will take a few days-weeks I advised that they can open full C of O and just do not trun on the fans until they are connected and tested. Fire alarm permit will remain open until connected. |
| 08/08/2017 |
FIRE - ALARM FINAL |
|
Partial Approval |
Note: Big A Fans need to be connected but they need a new data base for the fire alarm. Since this will take a few days-weeks I advised that they can open full C of O and just do not trun on the fans until they are connected and tested. |
| 08/04/2017 |
FIRE - ALARM FINAL |
|
Partial Approval |
Temp C of O ok for soft opening only. FA needs to verify that big fans shut down upon alarm event. |
| 07/31/2017 |
FIRE - ALARM FINAL |
|
Denied |
Needs plan and permit (B.A.F.) shut down, shut down the music |