Permit: T17CM04545

Parcel: 11616170B


Addresses:

620 W WILLIAMS ST

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
01/19/2018 FIRE SPKLR - FINAL Approved
12/28/2017 FIRE SPKLR - FINAL Denied 1) bell not wired correctly.
2) label bell breaker "fire bell."
3) add lockout to fire bell circuit breaker.
4) missing fdc. needs to be installed.
5) need knox fdc plug for fdc.
6) still need to flow water on next inspection. main drain test and inspectors test.
7) add calc plate to riser.
8) need spare head box mounted with heads and wrench inside.
9) system needs to be monitored.
Charlie 591-3943