Permit: T17CM04531

Parcel: 121110380

Inspection Status: Approved

Inspection History: PLUMBING - GAS RECONNECT

Date Description Inspector Results Comments
12/01/2017 PLUMBING - GAS RECONNECT Approved
11/22/2017 PLUMBING - GAS RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999


*
11/06/2017 PLUMBING - GAS RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999
1- THE GAS LINE DROP SUPPLY TO THE WATER HEATER AND FURNACE IN FRONT OF THE WATER HEATER AND WILL NOT ALLOW ACCESS FOR REMOVAL AND SERVICE. REFERENCE M1305.1 IRC.
2- THE SEDIMENT TRAP FOR THE FURNACE IS NOT LOCATED IN THE CORRECT LOCATION. THE SEDIMENT TRAP SHALL BE LOCATED DOWN STREAM OF THE SHUT OFF VALVE.
3- SHALL PROVIDE THE REQUIRED COMBUSTION AIR FOR THE FURNACE AND WATER HEATER.
4- RETEST THE GAS LINE SYSTEM.


*
10/16/2017 PLUMBING - GAS RECONNECT Denied IVRS - Inspection :
There is no access to the site.| 920


*