Permit: T17CM04456

Parcel: 133148320

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T17CM04456

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2017 FIRE - ALARM FINAL Approved
10/13/2017 FIRE - ALARM FINAL Denied Need synchronization
09/29/2017 FIRE - ALARM FINAL Denied not ready. did not do work per plans. did not test anything.
07/18/2017 FIRE - ALARM FINAL Denied -not ready
-needs to add notification
-annunciator not working
-needs to connect hvac duct smokes to panel